Chapter -4 Cooling Towers

Chapter - 4 Cooling Towers (Part 2 of 3)

 

Contents

Chapter - 4 Cooling Towers (Part 2 of 3) 1

.၈ အလုပ္လုပ္ပံု (Principle of Operation) 1

.၉ ဒီဇုိင္းအေျခအေနမ်ား (Design Conditions) 5

.၁၀ Cooling Tower Heat Transfer 6

.၁၁ Cooling Tower Performance Factor 8

.၁၂ Condenser Water Flow Rate. 9

.၁၃ စုပ္ယူသည့္အပူႏွင့္ စြန္႔ထုတ္သည့္ အပူပမာဏ တူညီျခင္း (Heat Balancing) 10

.၁၄ ေရြးခ်ယ္ရာတြင္ စဥ္းစားရမည့္ အခ်က္မ်ား (Selection Consideration) 11

 

.၈ အလုပ္လုပ္ပံု (Principle of Operation)

Cooling tower တြင္ water spray system ၊ fill packing material ႏွင့္ fan တို႔ ပါဝင္သည္။ Spray system သည္ ေရပူ(hot water)မ်ားကို fill packing ေပၚသို႔ ျဖန္းခ်သည္။ Cooling tower အတြင္း၌ ေလ ႏွင့္ ေရ ထိေတြ႔ေနသည့္ မ်က္ႏွာျပင္(contact surface)ဧရိယာ ပိုမ်ားလာရန္အတြက္ fill packing မ်ားကုိ အသံုးျပဳၾကျခင္း ျဖစ္သည္။ ေရပူ(hot water)မွ အပူမ်ား စြန္႔ထုတ္ရန္အတြက္ fan မ်ားသည္ ေလမ်ား(ambient air)ကို cooling tower အတြင္းသုိ႔ ဝင္ေရာက္ေအာင္ ေဆာင္ရြက္ေပးသည္။ Condenser water မွ စုပ္ယူ သယ္ေဆာင္ထားေသာ အပူမ်ားကို cooling tower အတြင္း sensible cooling ဖယ္ထုတ္ျခင္းနည္း ႏွင့္ ေရေငြ႔ ပ်ံေစျခင္းျဖင့္ အပူကို ဖယ္ထုတ္ျခင္း (evaporative cooling)နည္း ႏွစ္နည္း တုိ႔ျဖင့္ စြန္႔ထုတ္ပစ္ (reject)သည္။

Cooling tower မွ စြန္႔ထုတ္သည့္ အပူပမာဏ(amount of heat rejected)သည္ ဝင္လာသည့္ ေလ၏ Dry Bulb အပူခ်ိန္(sensible cooling ျဖစ္ရန္အတြက္)ႏွင့္ Wet Bulb အပူခ်ိန္(evaporative cooling ျဖစ္ရန္အတြက္)ေပၚတြင္ မူတည္သည္။

Condenser circuit တြင္ ပါဝင္ေသာ equipment မ်ားမွာ cooling tower ၊ condenser water pump ႏွင့္ chiller တုိ႔ ျဖစ္သည္။ Condenser water pump သည္ condenser water ကို chiller အတြင္းသုိ႔ တြန္းပို႔ သည္။ Condenser water သည္ chiller အတြင္းသုိ႔ ေရာက္ရွိၿပီး chiller အတြင္းမွ အပူမ်ားကို စုပ္ယူ ၿပီးေနာက္ condenser water အပူခ်ိန္ ျမင့္တက္လာသည္။ ထိုေနာက္ condenser water သည္ cooling tower သုိ႔ ေရာက္ရွိၿပီး အပူမ်ားကုိ ေလထုထဲသုိ႔ စြန္႔ထုတ္(reject)လိုက္ေသာေၾကာင့္ cooled water basin သုိ႔ ေရာက္သည့္အခါ condenser water ၏ အပူခ်ိန္ နိမ့္က်သြားသည္။ တစ္ဖန္ condenser water သည္ chiller အတြင္းမွ အပူမ်ားကို စုပ္ယူရန္ ျပန္လည္ ဝင္ေရာက္သြားသည္။ Chiller ၊ condenser water pump ႏွင့္ cooling tower တုိ႔ အတြင္း၌ condenser water အဆက္မျပတ္ လည္ပတ္ေနသည္။

Cooling tower တစ္လံုးသည္ အပူမ်ားကို

 

(၁)

ံံHeat transfer နည္း၊

 

(၂)

Mass transfer နည္း ႏွင့္

 

(၃)

Combination of heat and mass transfer နည္းတို႔ျဖင့္ အပူမ်ားကို စြန္႔ထုတ္(reject)သည္။

ဖိအားေျပာင္းလဲမႈ မရွိသည့္(constant pressure)အေျခအေနတြင္ အရည္(liquid)အျဖစ္မွ အေငြ႔ (vapor) အျဖစ္သုိ႔ အသြင္ေျပာင္းျခင္း(phase change)ကို “Vaporization” ဟုေခၚသည္။ ထုိ vaporization ျဖစ္သည့္ အခ်ိန္တြင္ စုပ္ယူသည့္ အပူကို “Latent Heat of Vaporization” ဟုေခၚသည္။ ေလထုဖိအား (atmospheric pressure)တြင္ ျဖစ္ေပၚလ်ွင္ “Latent Heat of Vaporization” at atmospheric pressure ဟု ေခၚသည္။ Cooling tower သည္ condenser water မွ အပူအခ်ိဳ႕ကို ေလထုအတြင္းသုိ႔ “Evaporative Cooling”နည္းျဖင့္ စြန္႔ထုတ္(reject) လုပ္သည္။ ထုိ႔ေၾကာင့္ ေရဆံုး႐ႈံးမႈ ျဖစ္ေပၚသည္။ ထိုဆံုး႐ႈံးသြားသည့္ ေရကို  “Evaporation Loss” ဟုေခၚသည္။ ေအာက္ပါ ပံု(၄-၂၅)သည္ counter flow cooling tower တစ္လံုး ၏ ေရ(condenser water)ႏွင့္ ေလအပူခ်ိန္ဆက္စပ္မႈ(temperature relationship)ကို ေဖာ္ျပထားသည္။

Condenser water အပူခ်ိန္ သည္ A မွ B သုိ႔ curve တြင္ ျပထားသည့္အတိုင္း နိမ့္ဆင္းသြားၿပီး ေလထု၏ Wet Bulb အပူခ်ိန္သည္ C မွ D သုိ႔ျမင့္တက္လာသည္။ Condenser water တြင္ အပူဆံုး႐ႈံးျခင္း(heat loss)ျဖစ္ၿပီး အနီးရွိေလထုတြင္ အပူတုိးျခင္း(heat gain) ျဖစ္ေပၚသည္။ Condenser water အပူခ်ိန္ ကြာျခားခ်က္(temperature difference)သည္ condenser water entering အပူခ်ိန္(cooling tower အတြင္း သုိ႔) မွ condenser water leaving အပူခ်ိန္(cooling tower မွ အထြက္)ကို ႏႈတ္ထားျခင္းျဖစ္သည္။  A အႏႈတ္ B ျဖစ္သည္။

ထုိအပူခ်ိန္ ကြာျခားခ်က္(temperature difference)ကို “Range” ဟု ေခၚသည္။ Steady-state အေျခအေနသုိ႔ ေရာက္ၿပီးခ်ိန္တြင္ range သည္ condenser water ၏ နိမ့္ဆင္း သြားေသာ အပူခ်ိန္ပင္ ျဖစ္သည္။

Air Conditioning, Heating, and Refrigeration Institute (AHRI)မွ စံ(standard)အျဖစ္ သတ္မွတ္ထားေသာ chiller မွ ထြက္လာသည့္(leaving from chiller) condenser water အပူခ်ိန္သည္ 35°C(95°F) ျဖစ္ၿပီး chiller အတြင္းသုိ႔ဝင္သည့္(entering into chiller) condenser water အပူခ်ိန္သည္  29.4°C(85°F)ျဖစ္သည္။ ထုိအခ်က္ကို မူတည္၍ cooling tower မ်ားကို ဒီဇုိင္းလုပ္ၾကသည္။

   အသံုးျပဳပံု(application)ႏွင့္ cooling tower ေရြးခ်ယ္ပံု(selection)ေပၚ မူတည္၍ ကြဲျပားမႈမ်ား ရွိႏုိင္သည္။

ပံု ၄-၂၅ Range ႏွင့္ Approch Temperature တုိ႔ကို ႏႈိင္းယွဥ္ ေဖာ္ျပထားပံု

Leaving condenser water ၏ အပူခ်ိန္(point B)ႏွင့္ အဝင္ေလ၏(entering) အပူခ်ိန္(point C) တုိ႔၏ ျခားနားခ်က္သည္ cooling tower ၏ “Approach” ပင္ျဖစ္သည္။ တစ္နည္းအားျဖင့္ ေလ၏ Wet Bulb အပူခ်ိန္သုိ႔ုိ႔႔႔႔႔႔႔ ေရာက္ေအာင္ ခ်ဥ္းကပ္ေနေသာေၾကာင့္ “Approach” ေခၚဆိုျခင္းျဖစ္သည္။ Approach သည္ cooling tower တစ္လံုး၏ အပူဖယ္ထုတ္ႏုိင္စြမ္း(capability) ျဖစ္သည္။

အလြန္ႀကီးမားေသာ(လုိအပ္သည္ထက္ ပိုႀကီးေအာင္ ျပဳလုပ္ထားေသာ) cooling tower မ်ားသည္ အလြန္ငယ္ေသာ approach (colder leaving water)ကို ေပးႏုိင္သည္။ (သတ္မွတ္ထားေသာ heat load ၊ flow rate ႏွင့္ entering air condition မ်ားအတြက္ သာျဖစ္သည္။) ေလထု(atmosphere) အတြင္းသုိ႔ စြန္႔ထုတ္ လုိက္ေသာ အပူပမာဏ(amount of heat transferred)သည္ heat load imposed on the tower ႏွင့္အျမဲ တူညီသည္။

Cooling tower တစ္လံုး၏ ကူးေျပာင္းႏုိင္သည့္ အပူပမာဏ(amount of heat transfer)သည္  ထို cooling tower ၏ အပူဖယ္ထုတ္ႏုိင္စြမ္း(thermal capability) ႏွင့္ ဝင္လာသည့္ေလ၏ အပူခ်ိန္ (entering air Wet Bulb temperature)တုိ႔ ေပၚတြင္ မူတည္သည္။ 
တစ္နည္းအားျဖင့္ cooling tower တစ္လံုး၏လုပ္ေဆာင္ႏုိင္စြမ္း(thermal capability)ေကာင္းေလ အပူမ်ားမ်ား စြန္႔္ထုတ္ပစ္ႏုိင္ေလ ျဖစ္သည္။ ဝင္လာသည့္ ေလ၏ အပူခ်ိန္(entering air Wet Bulb temperature) နိမ့္ေလ အပူစြန္႔ထုတ္ႏုိင္စြမ္း မ်ားေလ ျဖစ္သည္။

ဝင္ေလ(entering air)၏ Wet Bulb အပူခ်ိန္သည္ cooling tower တည္ရွိရာ ေဒသ၏ ရာသီဥတု ေပၚတြင္ မူတည္သည္။  Cooling tower တစ္လံုး၏ စြမ္းေဆာင္ရည္(thermal performance)သည္ ဝင္လာသည့္ ေလ၏ Wet Bulb အပူခ်ိန္ေပၚတြင္ အမ်ားဆံုး မူတည္သည္။ ဝင္လာသည့္ေလ၏ Dry Bulb အပူခ်ိန္ ႏွင့္ relative humidity သည္ mechanical draft cooling tower ၏ စြမ္းေဆာင္ရည္(thermal performance) အတြက္ အနည္းငယ္သာ အက်ိဳးသက္ေရာက္မႈ(insignificant effect) ရွိသည္။ Cooling tower တစ္လံုး၏ ေရဆံုး႐ႈံးမႈ နည္းျခင္း၊ မ်ားျခင္း (evaporation loss)ျဖစ္မႈ အေပၚတြင္ မူတည္သည္။ 

Cooling tower တစ္လံုး အတြင္းသို႔ ဝင္ေရာက္သြားေသာ ေလ၏ psychrometric analysis ကို ပံု(၄-၂၅) ႏွင့္ ပံု(၄-၂၆)တြင္ ေဖာ္ျပထားသည္။ ေလထု (ambient condition) (point A)တြင္ cooling tower တစ္လံုးအတြင္း ဝင္ေရာက္သြားၿပီးေနာက္ condenser water မွ heat ႏွင့္ mass(moisture)ကို စုပ္ယူ သြားသည္။ ထုိေနာက္ point B မွ တစ္ဆင့္ ထြက္သြားသည္။ ထုိ point B အေျခအေနသည္ saturated condition ျဖစ္သည္။ သုိ႔ေသာ္ သတ္မွတ္ထားသည့္ အပူစြန္႔ထုတ္ပစ္မႈ ပမာဏထက္နည္းသည့္အခါ(very light loads)မ်ိဳးတြင္ ထြက္သြားသည့္ ေလ(discharge air)သည္ fully saturated ျဖစ္ခ်င္မွ ျဖစ္ေပလိမ့္မည္။

ပံု ၄-၂၆ Cooling Tower တစ္လံုး၏ performance ကို psychrometric chart ေပၚတြင္ ေဖာ္ျပထားပံု

Condenser water မွ ေလသုိ႔ ကူးေျပာင္းသြားသည့္အပူ(heat transfer)ပမာဏသည္ cooling tower အတြင္းသုိ႔ ဝင္သြားသည့္ေလ၏ enthalpy (enthalpy of entering air)ႏွင့္ ထြက္သြားသည့္ ေလ၏ enthalpy (enthalpy of leaving air)ကြာျခားခ်က္ ျဖစ္သည္။ (hB − hA)ျဖစ္သည္။ အဘယ္ေၾကာင့္ဆိုေသာ္ enthalpy လုိင္းမ်ားသည္ Wet Bulb အပူခ်ိန္ လုိင္းမ်ားႏွင့္ အလြန္ နီးကပ္စြာ ရွိေနသာေၾကာင့္ျဖစ္သည္။ ေလ၏ enthalpy ေျပာင္းလဲမႈ(change in enthalpy of the air)သည္ ေလ၏ Wet Bulb အပူခ်ိန္ ေျပာင္းလဲမႈ ပင္ျဖစ္သည္။

ပံု(၄-၂၆)မွ Vector AB သည္ ေလထု(ambient air)၏ total heat gain ျဖစ္သည္။ Vector AB ကို component AC ႏွင့္ component CB အျဖစ္ ခြဲႏိုင္သည္။ Component AC သည္ sensible heat portion ျဖစ္သည္။ Component CB သည္ latent heat အပိုင္း ျဖစ္သည္။ ဝင္လာသည့္ေလသည္ point D သုိ႔ ေျပာင္းသြားခဲ့လ်ွင္ Wet Bulb အပူခ်ိန္ တူညီသည္။ သုိ႔ေသာ္ Dry Bulb အပူခ်ိန္ ပိုျမင့္သည့္အခါ total heat transfer(vector DB)သည္ တူညီလိမ့္မည္သာ ျဖစ္သည္။ Sensible အပုိင္း(components)ႏွင့္ latent အပုိင္း(component)တုိ႔သည္ မ်ားစြာ ေျပာင္းလဲသြားသည္။

DE သည္ ေလ၏ sensible cooling အပိုင္းျဖစ္သည္။ Condenser water သည္ အပူ(heat)ႏွင့္ ေရ(mass)အခ်ိဳ ့ကို ေလအတြင္းသုိ႔ စြန္ထုတ္မႈေၾကာင့္ EB သည္ latent heat ျဖစ္သည္။ ထို႔ေၾကာင့္ တူညီသည့္ water cooling load အတြက္ latent ႏွင့္ sensible heat တုိ႔ စြန္႔ထုတ္ပစ္သည့္ ပမာဏအခ်ိဳးသည္ မ်ားစြာ ေျပာင္းလဲႏုိင္သည္။ Latent heat ႏွင့္ sensible heat တုိ႔ စြန္႔ထုတ္သည့့္္ ပမာဏ အခ်ိဳးသည္ cooling tower တစ္လံုး ၏ ေရသံုးစဲြမႈ သို႔မဟုတ္ ေရဆံုး႐ႈံးမႈကို တြက္ခ်က္ရန္ အလြန္အေရးပါသည္။

Evaporation cooling နည္းျဖင့္ အပူမ်ားကို ဖယ္ထုတ္သည့္အခါ ေရမ်ား ဆံုးရ႐ံႈးသြားေသာေၾကာင့္ “Mass Transfer” နည္းျဖင့္ အပူကို ဖယ္ထုတ္ျခင္း ဟူ၍လည္း ေခၚဆုိေလ့ရွိသည္။ “Mass Transfer” နည္း သုိ႔မဟုတ္ Evaporation cooling နည္းသည္ latent heat အပုိင္းႏွင့္သာ သက္ဆုိင္ၿပီး specific humidity ေျပာင္းလဲမႈႏွင့္ တုိက္႐ုိက္ အခ်ိဳးက်သည္။

အဘယ္ေၾကာင့္ဆိုေသာ္ ဝင္လာသည့္ Dry Bulb အပူခ်ိန္ သုိ႔မဟုတ္ relative humidity သည္ latent to sensible heat transfer ၏ အခ်ိဳးေပၚတြင္ မူတည္ေသာေၾကာင့္ ျဖစ္သည္။ Latent to sensible heat transfer ၏ အခ်ိဳး(ratio)သည္ ေရေငြ႔ပ်ံႏႈန္း(rate of evaporation)အေပၚတြင္လည္း အက်ိဳးသက္ေရာက္မႈ ရွိသည္။

ပံု(၄-၂၆)တြင္ ျပထားသည့္အတိုင္း case AB(WB − WA)၏ ေရေငြ႔ပ်ံႏႈန္း(evaporation rate) သည္ case DB(WB − WD)၏ ေရေငြ႔ပ်ံႏႈန္း(rate of evaporation)ထက္နည္းသည္။ အဘယ္ေၾကာင့္ဆိုေသာ္ latent heat transfer(mass transfer)သည္ total heat transfer ၏ ေသးငယ္ေသာ ပမာဏျဖစ္ေသာေၾကာင့္ ျဖစ္သည္။

Cooling tower တစ္လံုး၏ ဒီဇုိင္း အေျခေနတြင္ ျဖစ္ႏုိင္ေသာ ေယဘုယ် ေရေငြ႔ပ်ံႏႈန္း(evaporation rate) သည္ ေရစီးႏွႈန္း(water flow)၏ ၁% ျဖစ္သည္။ 7 K of water temperature range ျဖစ္သည္။ ပ်မ္းမ်ွေရေငြ႔ပ်ံႏႈန္း(evaporation rate)သည္ ဒီဇုိင္းတြက္စဥ္က ေရေငြ႔ပ်ံႏႈန္း(design rate) ထက္ နည္းသည္။ အဘယ္ေၾကာင့္ဆိုေသာ္ ညဘက္ သုိ႔မဟုတ္ ေအးသည့္ရာသီတြင္ ဝင္လာေသာ ေလ၏ အပူခ်ိန္ က်ဆင္း လာသည္ႏွင့္အမ်ွ sensible component ပိုမ်ားလာၿပီး latent heat transfer (mass transfer) နည္းကာ ေရေငြ႔ပ်ံႏႈန္း(evaporation rate) နည္းျခင္းေၾကာင့္ ျဖစ္သည္။

ေရေငြ႔ပ်ံျခင္း (evaporation)ေၾကာင့္ ေရဆံုး႐ံႈးမႈ(water loss) ျဖစ္သည့္အျပင္ ပန္ကာေၾကာင့္ ေရစက္မ်ား လြင့္စင္ျခင္း(liquid carries over) ႏွင့္ ေရေဖာက္ထုတ္ျခင္း(blow down)စသည္ တုိ႔ေၾကာင့္လည္း ေရဆံုး႐ံႈးမႈ (water loss)မ်ား ျဖစ္ေပၚသည္။ ပန္ကာေၾကာင့္ ေရစက္မ်ား လြင့္စင္ျခင္း(liquid carry over) ႏွင့္ ေရေဖာက္ထုတ္ျခင္း(blow down) တုိ႔အေၾကာင္းကုိ ေနာက္ပုိင္းတြင္ ေဖာ္ျပထားသည္။

.၉ ဒီဇုိင္းအေျခအေနမ်ား (Design Conditions)

Cooling tower တစ္လံုး၏ လုပ္ေဆာင္ႏုိင္စြမ္း(thermal capability)ကို ေအာက္ပါ အခ်က္ (parameter) မ်ားျဖင့္ သတ္မွတ္သည္။

(က)

Cooling tower အတြင္းသုိ႔ ဝင္လာသည့္ condenser water ၏  အပူခ်ိန္ႏွင့္ ထြက္သြားသည့္ အပူခ်ိန္ (entering and leaving water temperatures)

(ခ)

ဝင္ေလ ၏ Wet Bulb ႏွင့္ Dry Bulb အပူခ်ိန္ ႏွင့္

(ဂ)

Condenser water ၏ ေရစီးႏႈန္း(flow rate)တုိ႔ ျဖစ္သည္။

မ်ားေသာအားျဖင့္ condenser water velocity အနည္းဆံုး 1.5 m/s မွ အမ်ားဆံုး 3.6 m/s အေျခခံ၍ condenser pipe အရြယ္အစားကို ေရြးခ်ယ္ေလ့ရွိသည္။

Evaporative cooling tower တုိင္း ေရေငြ႔ပ်ံျခင္း(evaporation)ျဖစ္သည့္ ေရပမာဏသည္ ဝင္လာသည့္ ေလ၏ Wet Bulb အပူခ်ိန္ႏွင့္ သက္ဆုိင္သည္။ Air conditioning တြင္ သံုးသည့္ cooling tower တစ္လံုး၏ အပူဖယ္ထုတ္ႏုိင္စြမ္း(thermal capability)ကို nominal capacity ျဖင့္ ေဖာ္ျပေလ့ရွိသည္။

လ်ွပ္စစ္ဓာတ္အားျဖင့္ ေမာင္းသည့္(electric) chiller ၏ evaporator မွ ၁ ကီလိုဝပ္(1kW) အေအးဓာတ္(cooling)ရရွိရန္ အတြက္ cooling tower  သည္ ခန္႔မွန္းေျခ ၁.၂၅ ကီလိုဝပ္(1.25 kW) ပမာဏ အပူကို ဖယ္ထုတ္(heat rejection)ေပးရန္ လိုအပ္သည္။

ေရစီးႏႈန္း(flow rate) 54 mLiter/sec ရိွသည့္ condenser water ၏ အပူခ်ိန္ 35°C(95°F)မွ 29.4°C(85°F)ေရာက္ေအာင္ လုပ္ႏုိင္လ်ွင္ တစ္ကီလိုဝပ္(1kW) အပူစြန္႔ထုတ္ျခင္း(heat rejection)ျဖစ္သည္။ ထုိအခ်ိန္တြင္ cooling tower အတြင္းသုိ႔ ဝင္ေရာက္လာေသာ ေလ၏ Wet Bulb အပူခ်ိန္သည္ 25.6°C ေပၚတြင္ အေျခခံသည္။ ထိုအေျခေနတြင္ တစ္ကီလုိဝပ္(1kW) evaporator cooling ရရွိရန္ ခန္႔မွန္းေျခ (၁.၂၅)ကီလုိဝပ္ (1.25 kW) ပမာဏရွိေသာ အပူကို cooling tower မွ စြန္႔ထုတ္(reject) ေပးရမည္။

လ်ွပ္စစ္ေမာ္တာျဖင့္ ေမာင္းသည့္(electric) chiller မွ တစ္ကီလုိဝပ္(1kW) cooling capacity ထုတ္ေပးတုိင္း cooling tower သည္ chiller မွ တစ္ကီလုိဝပ္(1kW)အျပင္ 0.25 kW of compressor heat ကိုပါ ဖယ္ထုတ္(reject) ေပးရသည္။ 0.25 kW of compressor heat ကို “Heat of Compression” ဟုလည္းေခၚသည္။ တစ္နည္းအားျဖင့္ 0.6 kW/RT efficiency ရွိသည့္ 500RT chiller မွ 500RT cooling capacity ကို ထုတ္ေပးေနခ်ိန္တြင္ cooling tower သည္ 500RT cooling capacity အျပင္ compressor မွထြက္သည့္ “Heat of Compression”  (500RT x 0.6 kW/RT = 300kW = 85RT) 85RT ကိုပါ စြန္႔ထုတ္ (reject) ေပးရသည္။ ထုိ႔ေၾကာင့္ cooling tower မွ 500RT+85RT= 585RT စြန္႔ထုတ္(reject) ေပးရသည္။ Condenser water pump မွ heat ကို ထည့္မတြက္ ထားပါ။ အခ်ိဳ႕ေသာ အေျခအေနမ်ားအတြက္ nominal capacity rating အတုိင္း အသံုးျပဳေလ့ မရွိသည္ကို ေတြ႔ရသည္။

အခ်ဳပ္အားျဖင့္ cooling tower တစ္လံုး၏ အပူဖယ္ထုတ္ႏုိင္စြမ္း(heat rejection capacity)ကို operating parameter မ်ား ျဖစ္ၾကေသာ ေရအဝင္အပူခ်ိန္(entering water temperature)၊ ေရအထြက္ အပူခ်ိန္(leaving water temperature) ၊ condenser water စီးႏႈန္း(flow rate)၊ ဝင္ေလ၏ (entering air) Wet Bulb အပူခ်ိန္ ႏွင့္ ေလစီးႏႈန္း( air flow rate) တု႔ိျဖင့္ ေဖာ္ျပသည္။

.၁၀ Cooling Tower Heat Transfer

 

ပံု ၄-၂၇

ပံု(၄-၂၇)တြင္ ေဖာ္ျပထားသည့္ condenser water ေရစက္ငယ္မွ အပူကို အနီးရွိေလ(surrounding air)ထဲသို႔ sensible heat transfer process ႏွင့္ latent heat transfer process နည္းႏွစ္မ်ိဳးလံုးျဖင့္ စြန္႔ထုတ္ပစ္ျခင္း ျဖစ္သည္။ ထို အပူကူးေျပာင္းျခင္းျဖစ္စဥ္(heat transfer process)ကို “Merkel Equation” ျဖင့္ ေဖာ္ျပႏိုင္သည္။

            Condenser water မွ ထြက္သြားသည့္ အပူ(heat)ပမာဏသည္ အနီးရွိေလ(surrounding air)မွ စုပ္ယူလိုက္သည့္ ပမာဏႏွင့္ ညီမ်ွသည္။

ပံု(၄-၂၈)တြင္ cooling tower characteristic ကို ဂရပ္ပံုစံျဖင့္ ေဖာ္ျပထားသည္။ Cooling tower characteristic ကို ေအာက္ပါအတုိုင္း ဂရပ္ပံုစံျဖင့္ ေဖာ္ျပသည့္နည္း(graphical representation)ျဖင့္လည္း ေလ့လာႏုိင္သည္။

Law of conservation of energy အရ  (cooling tower တစ္ခုလုံးကုိ control volume အျဖစ္ ယူဆလ်ွင္)

 

ပံု ၄-၂၈ Cooling tower တစ္လံုး၏ Enthalpy driving force ျဖင့္ ေဖာ္ျပထားပံု

C' သည္ ဝင္လာသည့္ေလ၏ enthalpy ျဖစ္သည္။

BC သည္ initial enthalpy driving force  ျဖစ္သည္။

CD  သည္ air operating line with slope L/G  ျဖစ္သည္။

DEF သည္ projecting the exiting air point onto the water operating line and then onto the temperature axis shows the outlet air Wet-Bulb temperature  ျဖစ္သည္။

L/G သည္ liquid to gas mass flow ratio (lb/lb or kg/kg) ျဖစ္သည္။

Condenser water မွ အပူဆုံး႐ႈံးမႈပမာဏ(heat loss)သည္ အနီးရွိေလထု(ambient air) မွ စုပ္ယူလိုက္သည့္အပူ(heat gain)ပမာဏ နွင့္ တူညီသည္။ Condenser water ၏ အပူဆုံး႐ႈံးမႈ(heat loss) ပမာဏသည္ Q_water  = m .Cp .Δt  ျဖစ္သည္။ 
Condenser water ၌ အပူခ်ိန္ေျပာင္းလဲမႈ(temperature change)ျဖစ္ေသာေၾကာင့္ sensible heat change သာ ျဖစ္ေပၚသည္။ သို႔ေသာ္ အနီးရွိေလထု(Ambient air)တြင္ sensible heat ႏွင့္ latent heat gain ႏွစ္မ်ိဳးေၾကာင့္ အပူတုိးလာျခင္း(heat gain) ျဖစ္ေပၚသည္။

တစ္နည္းအားျဖင့္ condenser water ကုိ sensible cooling ႏွင့္ ေရေငြ႔ပ်ံေစျခင္းျဖင့္ အပူကို ဖယ္ထုတ္ျခင္း (evaporative cooling)နည္း ႏွစ္မ်ိဳးျဖင့္ ေအးေစသည္။

t2

 =

Entering temperature of condenser water

t1

 =

Leaving temperature of condenser water

h2

 =

Enthalpy of leaving air

h1

 =

Enthalpy of entering air                                 

                           ကုိ water to air mass ratio သုိ႔မဟုတ္ liquid to gas mass flow ratio ဟုေခၚသည္။ ယူနစ္သည္ lb of water/lb of air သုိ႔မဟုတ္ kg of water/kg of air ျဖစ္သည္။

ေလထု(ambient air)အပူခ်ိန္ 78°F(25.5°C)DB ႏွင့္ 50% RH သည္ cooling tower အတြင္းသုိ႔ ေရာက္သည့္အခါ ေရေငြ႔ပ်ံေစၿပီး အပူကိုဖယ္ထုတ္ျခင္း(evaporative cooling)နည္းျဖင့္ condenser water ကုိ ေအးေစသည္။ ေလ၏ enthalpy သည္ 30.1 Btu/lb မွ 45.1 Btu/lb အထိ ျမင့္တက္သြားသည္။ 15 Btu/lb of dry air ျမင့္တက္သြားသည္။ ထုိ 15 Btu/lb သည္ condenser water အေလးခ်ိန္ တစ္ေပါင္ကုိ 15°F အပူအခ်ိန္ က်ဆင္းသြား ေစႏုိင္သည္။

ဝင္လာသည့္ေလ(ambient air)၏ စုိထုိင္းဆ(humidity ratio)သည္ 0.0103 lb of water vapor/lb of dry air ျဖစ္ၿပီး ထြက္သြားသည့္ ေလ၏ စုိထုိင္းဆ(humidity ratio)မွ 0.0233 lb of water vapor/lb or dry air ျဖစ္သည္။ ထုိ(0.0233lb - 0.0103=) 0.013 lb သည္ ေရေငြ႔ပ်ံ(evaporate)သြားသည့္ condenser water ျဖစ္သည္။

85°F ၌ ရွိေသာ latent heat vaporization တန္ဖိုးသည္ 1,045 Btu/lb(2260 KJ/kg) ျဖစ္သည္။  0.031lb x 1045 Btu/lb =13.6 Btu ျဖစ္သည္။ 15 Btu ၏ ၉၁% သည္ ေရေငြ႔ပ်ံေစျခင္းျဖင့္ အပူကို ဖယ္ထုတ္ျခင္း(evaporative cooling)နည္းေၾကာင့္ ျဖစ္ေပၚသည္။ က်န္သည့္ ၉% ခန္႔သည္ sensible cooling ေၾကာင့္ျဖစ္သည္။ Condenser water အပူခ်ိန္သည္ 15°F က်ဆင္းၿပီး ေလ၏ အပူခ်ိန္ 3.3°F ျမင့္တက္ လာသည္။ ေလ၏ အပူခ်ိန္သည္ 78°F မွ 81.3°F သုိ႔ ျမင့္တက္သည္။

.၁၁ Cooling Tower Performance Factor

Cooling tower တစ္လံုး၏ စြမ္းေဆာင္ရည္(performance)သည္ ေအာက္ပါ အခ်က္(factor or parameter) မ်ားေပၚတြင္ မူတည္သည္။
(၁)	Range	(၅)	Evaporation loss
(၂)	Approach	(၆) 	Cycles of concentration
(၃) 	Effectiveness	(၇)	Blow down losses ႏွင့္
(၄)	Cooling capacity	(၈)	Liquid/ Gas ratio တုိ႔ ျဖစ္သည္။

ပံု ၄-၂၉ Condenser water range ေျပာင္းလဲျခင္းေၾကာင့္cooling tower အရြယ္အစား ေျပာင္းလဲပုံကုိ ေဖာ္ျပထားသည္။

ေလ၏ Wet Bulb အပူခ်ိန္ ျမင့္တက္လာျခင္းေၾကာင့္ cooling tower ၏ စြမ္းေဆာင္ရည္ (performance) က်ဆင္းသြားသည္။ ေလ၏ Wet Bulb အပူခ်ိန္ ေျပာင္းလဲျခင္းေၾကာင့္ Approach တန္ဖိုး ေျပာင္းလဲသည္။ Range ေျပာင္းလဲျခင္းေၾကာင့္ Approach တန္းဖိုး ေျပာင္းလဲသည္။

 	Condenser water စီးႏႈန္း(flow rate)မ်ားျခင္း သုိ႔မဟုတ္ range မ်ားျခင္းေၾကာင့္ အပူ ဖယ္ထုတ္ ႏုိင္စြမ္း(heat rejection capacity) မ်ားလာသည္။

ပံု ၄-၃၀ Variation in tower size factor with range.

ပံု ၄-၃၁ Variation in tower size factor with condenser water flow rate.

အထက္ပါ ပံု(၄-၃၁)တြင္ condenser water စီးႏႈန္း(flow rate) ေျပာင္းလဲျခင္းေၾကာင့္ cooling tower အရြယ္အစား ေျပာင္းလဲပုံကုိ ေဖာ္ျပထားသည္။ အထက္ပါ ပံု(၄-၃၀) သည္ condenser water range ေျပာင္းလဲျခင္းေၾကာင့္ cooling tower အရြယ္အစား ေျပာင္းလဲပုံကုိ ေဖာ္ျပထားသည္။(Approach မေျပာင္းပါ။)

.၁၂ Condenser Water Flow Rate

Condenser water system တြင္ စီးႏႈန္း(flow rate)သည္ အလြန္ အေရးႀကီးသည္။ Condenser water မွ အပူ(heat)မ်ား ေလထု(ambient air)ထဲသို႔ အပူစြန္႔ထုတ္ျခင္း(heat rejection) ျဖစ္ေစရန္ လံုေလာက္ ေသာ condenser water စီးဝင္လည္ပတ္မႈ ရိွ၊ မရိွ စစ္ေဆးရန္ လိုအပ္သည္။ ေယဘုယ်အားျဖင့္ “Range” ကို 5.6°C (95°F - 85°F = 10°F)တန္ဖိုးတြင္ အေျခခံ၍ ဒီဇိုင္းျပဳလုပ္ၾကသည္။

Cooling capacity 1 RT လ်ွင္ condenser water ေရလည္ပတ္ႏႈန္းသည္ 0.19 Liter/Sec (3GPM) ျဖစ္ၿပီး Chilled water ေရလည္ပတ္ႏႈန္းသည္ 2.4 GPM ျဖစ္သည္။ ထို႔ေၾကာင့္ condenser water ေရလည္ပတ္ႏႈန္း(flow rate)သည္ chilled water ေရလည္ပတ္ႏႈန္း(flow rate)၏ (၁.၂၅)ဆ(1.25 times) ျဖစ္သည္။ ၂၅% ပိုမ်ားသည္။ Chilled water စီးႏႈန္း(flow rate)သည္ 0.15 Liter/Sec per RT သုိ႔မဟုတ္ 2.4 GPM per RT ျဖစ္သည္။

            တစ္နည္းအားျဖင့္ electric chiller မ်ားတြင္ heat of compression သည္ chiller cooling load ၏ 25% နီးပါးႏွင့္ ညီမ်ွေသာေၾကာင့္ျဖစ္သည္။

အကယ္၍ condenser water စီးႏႈန္း(flow rate)သည္ လိုအပ္သည္ထက္ နည္းလ်ွင္ condenser water return temperature ျမင့္တက္လာလိမ့္မည္။ Chiller အတြင္းသို႔ အပူခ်ိန္ျမင့္သည့္ condenser water ဝင္ေရာက္လာလ်ွင္ refrigerant ၏ condensing pressure ျမင့္တက္လာၿပီး compressor ၏ စြမ္းအင္ သံုးစြဲမႈ(power consumption) ပိုမ်ား လာလိမ့္မည္။

လံုေလာက္ေသာ ေရစီးႏႈန္း(water flow rate) ကို chiller အတြင္းသုိ႔ လည္ပတ္ေစျခင္းေၾကာင့္ condenser water return temperature က်ဆင္းလာကာ chiller efficiency ပိုေကာင္း လာလိမ့္မည္။

 

Air-Conditioning, Heating, and Refrigeration Institute (AHRI) သတ္မွတ္ ခ်က္အရ ဒီဇုိင္းအေျခအေန(design condition) တြင္ cooling capacity 1 RT ရရန္ condenser water ေရလည္ပတ္ႏႈန္း(flow rate)သည္ 0.19 Liter/Sec per RT သုိ႔မဟုတ္ 3 GPM per RT ျဖစ္သည္။

 

Lower part load အေျခအေနမ်ိဳးတြင္လည္း condenser water စီးႏႈန္း(flow rate)ကို ဒီဇုိင္း စီးႏႈန္း (design flow rate)ထက္ အနည္းငယ္ ေလ်ာ့နည္း ေအာင္ ေလ်ွာ့ခ်ႏုိင္သည္။

ပံု ၄-၃၂ Condenser and chilled water circuit

         Actual condenser water စီးႏႈန္း(flow rate) သည္ design condenser water စီးႏႈန္း(flow rate) ထက္ ပိုမမ်ားရန္ လိုအပ္သည္။ Condenser water စီးႏႈန္း(flow rate) လုိအပ္သည္ထက္ ပိုမ်ားျခင္းေၾကာင့္ ပန္႔္႔အတြက္ လုိအပ္ေသာစြမ္းအင္(pumping power)ကို ျဖဳန္းတီးရာ ေရာက္သည္။ တစ္နည္းအားျဖင့္ over pumping ျဖစ္ေစသည္။

Cooling tower စြမ္းေဆာင္ရည္ (performance) ည့ံဖ်င္းေနလ်ွင္ condenser water စီးႏႈန္း(flow rate)မ်ားျခင္း ေၾကာင့္လည္း condenser water supply temperature ျမင့္တက္လာႏုိင္သည္။ Cooling tower တစ္ခုခ်င္းစီ တူညီေသာေရပမာဏ စီးဝင္ျခင္း(flow)မရိွသည့္အခါ (unbalance water flow ျဖစ္ျခင္းေၾကာင့္) အခ်ိဳ႕ cooling towerသည္ ဒီဇုိင္းစီးႏႈန္း(design flow rate)ထက္ပိုမ်ားသည့္ condenser စီးႏႈန္း(flow rate)ကို ရရိွကာ အထြက္ေရအပူခ်ိန္(condenser water supply temperature) ပိုျမင့္မားလာသည္။ အထြက္ေရ အပူခ်ိန္(condenser water supply temperature) ျမင့္ေသာေၾကာင့္ chiller efficiency က်ဆင္းလိမ့္မည္။

.၁၃ စုပ္ယူသည့္အပူႏွင့္ စြန္႔ထုတ္သည့္ အပူပမာဏ တူညီျခင္း (Heat Balancing)

Vapor compression cycle မ်ားတြင္ evaporator က အပူ(heat)ကိုစုပ္ယူသည့္ အလုပ္လုပ္ၾကၿပီး condenser မ်ားက ထိုစုပ္ယူထားေသာ အပူကိုျပန္စြန္႔ထုတ္ျခင္း(heat rejection)လုပ္ၾကသည္။ Compressor အတြင္းမွ အပူခ်ိန္ျမင့္ၿပီး ဖိအားျမင့္သည့္(hot and high pressure) refrigerant gas မ်ားသည္ condenser အတြင္းသို႔ ေရာက္ရိွလာၿပီး နည္း ႏွစ္မ်ိဳးျဖင့္ အပူဖယ္ထုတ္ျခင္း(heat rejection)လုပ္ၾကသည္။

ထို refrigerant gas သည္ superheat အပူခ်ိန္၌ အေငြ႕(vapor) အေျခအေနျဖင့္ sensible heat ကို စြန္႔ထုတ္(reject)သည္။ ထို႔ေနာက္ saturated အပူခ်ိန္၌ latent heat ကို စြန္႔ထုတ္(reject)ကာ refrigerant အေငြ႕ (vapor)မွ အရည္(liquid)အျဖစ္သို႔ ေျပာင္းသြားသည္။

Condenser load သည္ ဖယ္ထုတ္သည့္အပူပမာဏ(amount of heat rejection) ျဖစ္သည္။ Air cooled condenser မွ အပူဖယ္ထုတ္ျခင္း(heat rejection)ေၾကာင့္ ေလ၏အပူခ်ိန္ ျခားနားခ်က္ 9°C မွ 12°C ခန္႔ ျမင့္တက္ လာေအာင္ ဒီဇိုင္းလုပ္ေလ့ ရိွသည္။ အကယ္၍ အပူခ်ိန္ျမင့္တက္မႈ(temperature raise) 10.5°C ကို အေျခခံ၍ တြက္လ်ွင္ 1kW  အပူပမာဏကို စြန္႔ထုတ္(reject)ရန္အတြက္ ေလစီးႏႈန္း 0.093 kg (mass flow rate 0.093 kg/kW)လိုအပ္သည္။ [1/(10.5x1.02)= 0.093 kg/kW]

ဥပမာအားျဖင့္ ႐ံုးခန္းတစ္ခု၏ air con unit သည္ 350kW cooling capacity ရိွၿပီး 430kW အပူပမာဏ ဖယ္ထုတ္ျခင္း(heat rejection)ျဖစ္ရန္ ေလစီးႏႈန္း(flow rate) 40.85 kg/s သို႔မဟုတ္ 36 m3/s ရိွသည့္ air-cooled condenser ကို အသံုးျပဳရမည္။ ေလျဖင့္ အပူစြန္႔ထုတ္သည့္အခါ ေရထက္ volume flow rate သုိ႔မဟုတ္ mass flow rate ပိုမ်ားေသာေၾကာင့္ ေနရာက်ယ္က်ယ္ လိုအပ္သည္။

ပံု ၄-၃၃ Heat Balance    

ပံု ၄-၃၄ Heat Balance    

           

            ဥပမာ condenser တစ္ခုသည္ အပူ(heat)ပမာဏ 12kW ကို ဖယ္ထုတ္(reject)ရန္အတြက္ အပူခ်ိန္ 35°C ရိွေသာ ျပင္ပေလ(outdoor air) သည္ အပူခ်ိန္ 50°C အထိ ျမင့္တက္သြားသည္။ ထို condenser သည္ 8 kW အပူပမာဏကို ဖယ္ထုတ္(reject)ရန္ လိုအပ္ၿပီး ျပင္ပေလ(outdoor air)သည္ 15°C ျဖစ္လ်ွင္ အပူခ်ိန္မည္မ်ွွ အထိတက္ သြားမည္နည္း။

Temperature difference = 50 ̊ C – 35 ̊ C = 15 ̊ C

                                                               = 12 kW/15°C  =  0.8 kW/ ̊ C

ပံု ၄-၃၅  Carnot cycle for refrigeration          

ထို condenser သည္ 1°C အပူခ်ိန္ကြာျခားတိုင္း(temperature difference) အပူပမာဏ 0.8 kW ကို ဖယ္ထုတ္(reject) ႏိုင္စြမ္းရွိသည္။

.၁၄ ေရြးခ်ယ္ရာတြင္ စဥ္းစားရမည့္ အခ်က္မ်ား (Selection Consideration)

မိမိ၏ လုပ္ငန္း(application)ႏွင့္ သင့္ေလ်ာ္မွန္ကန္ေသာ cooling tower ကို ေရြးခ်ယ္အတြက္ ေအာက္ပါ အခ်က္အလက္မ်ားကိုိ ထည့္သြင္းစဥ္းစားရန္ လိုအပ္သည္။

(က)

Cooling duty (လုိအပ္ေသာ အပူဖယ္ထုတ္ႏႈန္း(capacity) ၊ ေမာင္းႏွင္မည့္ duty အမ်ိဳးအစား)

(ခ)

Economics [စီးပြားေရးတြက္ေခ်ကိုက္မႈ၊ တပ္ဆင္ရန္ကုန္က်စရိတ္(installation cost) ၊ ေမာင္းႏွင့္ လည္ပတ္ရန္ ကုန္က်စရိတ္ (operation cost)]

(ဂ)

Required services (လုိအပ္သည့္ ဆားဗစ္အမ်ိဳးအစားမ်ား)

(ဃ)

Environmental conditions (ပတ္ဝန္းက်င္ကို ထိခိုက္မႈရွိ မရွိ၊ ေက်ာင္း၊ ေဆး႐ုံ သုိ႔မဟုတ္ လူအမ်ားစု ႏွင့္ နီးသည့္ေနရာတြင္ cooling tower ကို တပ္ဆင္ရန္ မသင့္ေလ်ာ္ေပ။ Legionella ပိုးမႊား (pathogenic gram)အႏၲရာယ္ေၾကာင့္ ျဖစ္သည္။) Legionella အေၾကာင္း အေသးစိတ္ သိလုိပါက

 http://www.nea.gov.sg/cms/qed/cop_legionella.pdf  တြင္ ေလ့လာႏုိင္သည္။

(င)

Maintenance requirements (ျပဳျပင္ထိန္းသိမ္းရန္ လုိအပ္ခ်က္မ်ား) ႏွင့္

(စ)

Aesthetics- အျမင္လွပမႈ ရွိ၊ မရွိ တုိ႔ျဖစ္သည္။ (လူျမင္ကြင္းတြင္ တပ္ဆင္ထားေသာ cooling tower မ်ားအား ၾကည့္ေကာင္းေအာင္ ျပဳလုပ္ထားရန္ သုိ႔မဟုတ္ ကာရံထားရန္ လိုအပ္သည္။)

အထက္ပါ အခ်က္အလက္မ်ားသည္ တစ္ခုႏွင့္တစ္ခု အျပန္အလွန္ဆက္စပ္မႈ ရွိၾကသည္။  တစ္ခုခ်င္းစီကို ဆန္းစစ္ေရြးခ်ယ္ ရမည္။

အထက္ပါ အခ်က္္မ်ားအျပင္ cooling tower ေရြးခ်ယ္ျခင္းႏွင့္ သက္ဆုိင္ေသာ အခ်က္အလက္မ်ားမွာ

(၁)

Safety features ၊ safety codes ႏွင့္ သက္ဆိုင္ေသာ ေဘးရန္ကင္းရွင္းေရး စည္းမ်ည္း စည္းကမ္း မ်ားကို လိုက္နာရမည္။

(၂)

အေဆာက္အဦ အမ်ိဳးအစားကို လိုက္၍ ခ်မွတ္ထားသည့္ code မ်ားကို လိုက္နာရမည္။ (Conformity to building codes)

(၃)

General design and rigidity of structures (တည္ေဆာက္မည့္ structure ဒီဇုိင္း ႏွင့္ အမ်ိဳးအစား)

(၄)

Relative effects of corrosion, scale, or deterioration on service life (သံေခ်းတက္ျခင္း၊ ေရညိႇ တက္ျခင္း၊ စြမ္းရည္က်ဆင္းျခင္း ႏွင့္ အသံုးျပဳႏုိင္သည့္ သက္တမ္းတုိျခင္း စသည္တုိ႔ႏွင့္ သက္ဆုိင္ေသာ အခ်က္မ်ား)

(၅)

Availability of spare parts (အပုိပစၥည္းမ်ား အလြယ္တကူ ရရွိႏုိင္မႈ)

(၆)

Experience and reliability of manufacturers (ထုတ္လုပ္သူ၏ လုပ္ငန္းအေတြ႔အၾကံဳႏွင့္ စိတ္ခ်ႏုိင္မႈရွိ ၊ မရွိ)

(၇)

Independent certification of thermal ratings (ေဖာ္ျပထားေသာ စြမ္းေဆာင္ရည္ႏႈန္း(rating)မ်ား ကို ထုတ္လုပ္သူမဟုတ္သည့္ တျခားေသာအဖြဲ႔ တစ္ခုခုမွ ေထာက္ခံေပးမႈ)

(၈)

Operating flexibility for economical operation at varying loads or during seasonal changes. (ေႏြ၊မိုး၊ေဆာင္း ရာသီဥတုအားလံုး၌ ျဖစ္ေပၚႏုိင္သည့္ load မ်ား အားလံုး ႏွင့္ ကိုက္ညီေအာင္ ေမာင္းႏုိင္မႈ)တုိ႔ ျဖစ္သည္။

ထိုအခ်က္အလက္မ်ားအျပင္ တုန္ခါမႈ(equipment vibration)၊ ဆူညံသံ(sound levels) ၊ ဆူညံသံေလ်ာ့နည္းေအာင္ ေဆာင္ရြက္ျခင္း(acoustical attenuation)၊ ဗိသုကာဒီဇုိင္း(architectural design) ႏွင့္ လိုက္ေလ်ာ ညီေထြျဖစ္မႈ တုိ႔ကိုလည္း အဓိကထား စဥ္းစားရမည္ ျဖစ္သည္။

Cooling duty ႏွင့္သက္ဆုိင္ေသာ အခ်က္အလက္မ်ားသည္ အျမင့္(height)၊ အရွည္(length)၊ အထူ (width)၊  ေလလည္ပတ္ႏႈန္း(volume of airflow)၊  fan ႏွင့္ pump တုိ႔၏ စြမ္းအင္သံုးစြဲမႈႏွုန္း(energy consumption)၊ တည္ေဆာက္ထားသည့္ ပစၥည္းအမ်ိဳးအစား(materials of construction)၊ ေရအရည္­အေသြး (water quality) ႏွင့္ ေစ်းကြက္တြင္ ရရွိႏုိင္မႈ(availability)တုိ႔ ျဖစ္သည္။

မိမိအေဆာက္အဦ သုိ႔မဟုတ္ မိမိ system အတြက္ အေကာင္းဆံုးႏွင့္ အသင့္ေလ်ာ္ဆံုးေသာ cooling tower အမ်ိဳးအစားႏွင့္ အရြယ္အစားကို economic evaluation လုပ္ၿပီးမွသာ ရရွိႏုိင္သည္။ နည္းပညာအရ (technically) အသင့္ေလ်ာ္ဆံုးျဖစ္ရန္ လုိအပ္သလုိ စီးပြားေရအရ(economically)လည္း အက်ိဳးအျမတ္ မ်ားရန္ လုိအပ္သည္။

2007 ASHRAE Handbook စာအုပ္မွ Chapter 36 ပါရွိေသာ HVAC Applications အပုိင္းတြင္ အသံုးမ်ားသည့္ စီးပြားေရးအရ တြက္ေျခကုိက္မႈ ရွိ၊မရွိ ဆန္းစစ္နည္း(economic evaluation) ႏွစ္မ်ိဳးကို ေဖာ္ျပ ထားသည္။

 (၁)

Life Cycle Costing (equipment တစ္ခု စဝယ္သည့္ေန႔မွ သံုးမရ၍ ဖ်က္ပစ္သည့္ေနအထိ ကုန္က် စရိတ္ စုစုေပါင္းကို တြက္သည့္နည္း)ႏွင့့္

(၂)

Payback analysis (ဝယ္ၿပီး တပ္ဆင္ရန္ ကုန္က်စရိတ္မ်ားကို ျပန္လည္ရရွိရန္ ႏွစ္မည္မ်ွွၾကာသည္ကို တြက္သည့္နည္း ျဖစ္သည္။)

အထက္ပါ နည္းႏွစ္နည္း အနက္မွ ႀကိဳက္ႏွစ္သက္ရာ နည္းကုိ အသံုးျပဳႏုိင္သည္။

            အစပုိင္းကုန္က်စရိတ္မ်ား (initial cost) အတြက္ ေအာက္ပါ အခ်က္အလက္တုိ႔ကို ထည့္သြင္း စဥ္းစား သင့္သည္။

Erected cost of equipment (ျငမ္း၊ ကရိန္း စသည့္တို႔အတြက္ ကုန္က်စရိတ္)

Costs of interface with other subsystems (သက္ဆုိင္သည့္ တျခားေသာ subsystem မ်ားႏွင့္ interface လုပ္ရန္ ကုန္က်စရိတ္)

Pumps and prime movers (ပန္႔ စသည့္ တုိ႔အတြက္ကုန္က်စရိတ္)

Electrical wiring to pump and fan motors (ပန္႔ ၊ ေမာ္တာ ႏွင့္ fan ေမာ္တာ တုိ႔၏ လ်ွပ္စစ္ဝါယာႏွင့္ သက္ဆုိင္ေသာ ကုန္က်စရိတ္)

Electrical controls and switchgear (လ်ွပ္စစ္ panel မ်ား ႏွင့္ control မ်ား၊ switchgear တို႔ အတြက္ ကုန္က်စရိတ္)

Piping to and from the tower (ပိုက္မ်ား တပ္ဆင္ရန္အတြက္ ကုန္က်စရိတ္)

Tower basin ၊ sump screens ၊ overflow piping and makeup lines ၊ if not furnished by the manufacturer (တျခားေသာ အစိတ္အပိုင္းမ်ား အတြက္ ကုန္က်စရိတ္)

Shutoff and control valves (ဘားမ်ားအတြက္ ကုန္က်စရိတ္)

Walkways ၊ ladders ၊ etc., providing access to the tower ၊ if not furnished by the manufacturer (ေလ်ွာက္လမ္း၊ ေလွကားတို႔အတြက္ ကုန္က်စရိတ္)

Fire protection sprinkler system (မီးေဘးကာကြယ္ေရး အစီအမံမ်ားအတြက္ ကုန္က်စရိတ္)

ပုိင္ဆုိင္မႈအတြက္ ကုန္က်စရိတ္(ownership cost)ႏွင့္ ထိန္းသိမ္းျပဳျပင္မႈ ကုန္က်စရိတ္(maintenance costs) တို႔အတြက္ ေအာက္ပါ အခ်က္အလက္တုိ႔ကို ထည့္သြင္း စဥ္းစားသင့္သည္။

System energy costs (fans, pumps, etc.) (တစ္နာရီေမာင္းရန္အတြက္ လိုအပ္သည့္ စြမ္းအင္ အတြက္ ကုန္က်စရိတ္)

Energy demand charges (လ်ွပ္စစ္ဓာတ္အားခ ကုန္က်စရိတ္)

Expected equipment life (အေမ်ွာ္လင့္ႏုိင္ဆံုးေသာ အသံုးျပဳႏုိင္မည့္ သက္တမ္း)

Maintenance and repair costs (ထိန္းသိမ္းစရိတ္ ႏွင့္ ျပဳျပင္စရိတ္)

Money costs (အတုိးတြက္၊ ေငြေၾကးေဖာင္းပြမႈ စသည့္တုိ႔အတြက္ ထည့္ေဆာင္းရမည့္ စရိတ္)

End of Part 2 of 3

 

 

 

 

 

Air Conditioning and Mechanical Ventilation System (Vol. 1) ႏွင့္သက္ဆုိင္ေသာ ACMV Lecture မ်ား (18 Lectures)
1 Chapter-1 Fundamental and Basic Concept Read
2 Chapter-2 (Part 1 of 3) Understanding Psychrometrics (Part 1 of 3) Read
3 Chapter-2 (Part 2 of 3) Understanding Psychrometrics (Part 2 of 3) Read
4 Chapter-2 (Part 2 of 3) Understanding Psychrometrics (Part 3 of 3) Read
5 Chapter - 3 Air Handling Units (Part 1 of 2) Chapter - 3 Air Handling Units (Part 1 of 2) Read
6 Chapter - 3 Air Handling Units (Part 2 of 2) Chapter - 3 Air Handling Units (Part 2 of 2) Read
7 Chapter - 4 (Part 1 of 3) Cooling Towers (Part 1 of 3) Read
8 Chapter - 4 (Part 2 of 3) Cooling Towers (Part 2 of 3) Read
9 Chapter - 4 (Part 3 of 3) Cooling Towers (Part 3 of 3) Read
10 Chapter - 5 (Part 1 of 3) Air Distribution Systems (Part 1 of 3) Read
11 Chapter - 5 (Part 2 of 3) Air Distribution Systems (Part 2 of 3) Read
12 Chapter - 5 (Part 3 of 3) Air Distribution Systems (Part 3 of 3) Read
13 Chapter - 6 (Part 1 of 3) Fans and Blowers (Part 1 of 3) Read
14 Chapter - 6 (Part 2 of 3) Fans and Blowers (Part 2 of 3) Read
15 Chapter - 6 (Part 3 of 3) Fans and Blowers (Part 3 of 3) Read
16 Chapter-7 ( Part 1 of 3) Ventilation ( Part 1 of 3) Read
17 Chapter-7 ( Part 2 of 3) Ventilation ( Part 2 of 3) Read
18 Chapter-7 ( Part 3 of 3) Ventilation ( Part 3 of 3) Read
   

www.acmv.org - Air Conditioning and Mechanical Ventilation for Young Myanmar Engineers

To download all ACMV lecuters in PDF format